Normal environment
ISG-100
Order number: A04078two M8 bolts with nuts
- encapsulated high-performance isolating spark gap
- for indirect connection (earthing) of isolated conductive parts under lightning conditions, where direct connection is not allowed
Technical parameters
| Parameter name | Parameter value | |
|---|---|---|
| Classification | class N - normal duty | |
| Isolation resistance | 100.00 MOhm | |
| Lightning impulse current | Iimp | 50.00 kA | 
| Rated impulse sparkover voltage | Uimp | 0.95 kV | 
| Rated power frequency withstand voltage | UWAC | 0.070 kV | 
| Rated DC withstand voltage | UWDC | 0.100 kV | 
| Degree of protection | IP 67 | |
| Range of ambient temperatures (min/max) | -40 / 80 °C | |
| According to standard | EN 62561-3:2012,IEC 62561-3:2012 | |
| ETIM Class | EC000510 | |
| Customs tariff number | 85363090 | |
| EAN | 8595090540786 |