DA-075-DJ25



DA-075-DJ25

Describe first line 
visual fault signalling
Product description 
universally applicable SPD for all types of LV electric and electronic equipments against surge voltage, installation to LV installations, close to protected equipment, for protection of the equipments against impact of induced overvoltages during a lightning strike or switching overvoltages
Ordering number 
A06094
Dimension drawing
Basic circuit diagram
Technical specifications
Type of network 
TN
Type of SPD 
T3
Nominal voltage 
Un
60
V AC
Maximum operating voltage 
Uc
75,00
V AC
Nominal load current 
IL
25,000
A
Nominal discharge current (8/20 µs) L-N 
In
2,00
kA
Nominal discharge current (8/20 µs) N-PE 
In
2,00
kA
Nominal discharge current (8/20 µs) L+N-PE 
In
2,00
kA
Test voltage L-N 
Uoc
4,0
kV
Test voltage N-PE 
Uoc
4,0
kV
Test voltage L+N-PE 
Uoc
4,0
kV
Voltage protection level mode L-N 
Up
0,43
kV
Voltage protection level mode N-PE 
Up
0,75
kV
Voltage protection level mode L-PE 
Up
0,75
kV
Short-circuit current rating 
ISCCR
1,5
kA
Maximum overcurrent protection 
25 A gL/gG or B 25 A
Response time L-N 
ta
25
ns
Response time N-PE 
ta
100
ns
TOV 5 s L-N 
120
V
TOV characteristic (TOV 5 s) 
withstand
Cross-section of connected conductors solid (max) 
6,00
mm2
Cross-section of connected conductors stranded (max) 
6,00
mm2
Fault indication 
red indicator
Degree of protection 
IP 20
Range of ambient temperatures - min 
-40
°C
Range of ambient temperatures - max 
80
°C
Mounting 
DIN rail 35 mm
According to standard 
EN 61643-11:2012, IEC 61643-11:2011
ETIM Class 
EC000942
Customs tariff number 
85363010
EAN 
8595090560944

Other products in this category

Ordering number:
A06095
surge protection for TN and TT systems, installation close to protected equipment, 25 A, up to 150 V AC
Ordering number:
A01872
single-phase surge protection connected in the 1+1 mode for TN and TT systems, installation close to protected equipment, 63 A, pluggable modules
Ordering number:
A01975
single-phase surge protection connected in the 1+1 mode for TN and TT systems, installation close to protected equipment, 63 A, pluggable modules, pluggable module, remote fault signalling
Ordering number:
A01848
three-phase surge protection connected in the 3+1 mode for TN and TT systems, installation close to protected equipment, 63 A, pluggable modules
  •  
  • 1 of 2
  • >