SLP-075 V/1

SLP-075 V/1

Describe first line 
pluggable module, visual fault signalling
Product description 
varistor surge arrester, installation to LV installations, especially to sub-distribution boards, for protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages
Ordering number 
A01815
Dimension drawing
Basic circuit diagram
Technical specifications
Type of SPD 
T2
Nominal voltage 
Un
60
V AC
Maximum operating voltage 
Uc
75,00
V AC
Maximum operating voltage 
Uc
100,00
V DC
Nominal discharge current (8/20 µs) 
In
15,00
kA
Maximum discharge current (8/20 µs) 
Imax
40,00
kA
Voltage protection level at 5 kA 
Up
0,30
kV
Voltage protection level 
Up
0,40
kV
Short-circuit current rating 
ISCCR
50,0
kA
Maximum overcurrent protection 
160 A gL/gG
Response time 
ta
25
ns
TOV 5 s L-N 
90
V
TOV characteristic (TOV 5 s) 
withstand
Cross-section of connected conductors solid (min) 
1,00
mm2
Cross-section of connected conductors solid (max) 
35,00
mm2
Cross-section of connected conductors stranded (min) 
1,00
mm2
Cross-section of connected conductors stranded (max) 
25,00
mm2
Fault indication 
red indication field
Degree of protection 
IP 20
Range of ambient temperatures - min 
-40
°C
Range of ambient temperatures - max 
80
°C
Mounting 
DIN rail 35 mm
According to standard 
EN 61643-11:2012, IEC 61643-11:2011
Plug module 
SLP-075 V/0
ETIM Class 
EC000941
Customs tariff number 
85363030
EAN 
8595090518150

Other products in this category

Ordering number:
A01823
surge arrester for TN and TT systems, up to 75 V AC, 40 kA (8/20 µs), remote fault signalling
Ordering number:
A05185
surge arrester for TN and TT systems, up to 150 V AC, 40 kA (8/20 µs)
Ordering number:
A05186
surge arrester for TN and TT systems, up to 150 V AC, 40 kA (8/20 µs), remote fault signalling
Ordering number:
A01617
surge arrester for TN and TT systems, 40 kA (8/20 µs)
  •  
  • 1 of 6
  • >