ISGO-500

ISGO-500

Describe first line
connecting cable and M8 bolt with nut
Product description
  • encapsulated high-performance isolating spark gap
  • for indirect connection (earthing) of isolated conductive parts under lightning conditions, where direct connection is not allowed
Ordering number
A05518
Dimension drawing
Basic circuit diagram
Technical specifications
Lightning impulse current
Iimp
100,00
kA
Rated impulse sparkover voltage
Uimp
1,50
kV
Rated power frequency withstand voltage
UWAC
0,350
kV
Rated DC withstand voltage
UWDC
0,500
kV
Isolation resistance
100,00
MOhm
Classification
class H - heavy duty
Degree of protection
IP 67
Range of ambient temperatures - min
-40
°C
Range of ambient temperatures - max
80
°C
According to standard
EN 62561-3:2012,IEC 62561-3:2012
ETIM Class
EC000510
Customs tariff number
85363090
EAN
8595090555186

Other products in this category

Ordering number:
A04078
  • isolation spark gap
  • 50 kA (10/350 µs), screws, withstand voltage 100 V DC
Ordering number:
A04086
  • isolation spark gap
  • 50 kA (10/350 µs), screws, withstand voltage 50 V DC
Ordering number:
A04127
  • isolation spark gap
  • 100 kA (10/350 µs), class H, screws, withstand voltage 500 V DC
Ordering number:
A03590
  • isolation spark gap
  • 100 kA (10/350 µs), class H, pins
  •  
  • 1 of 2
  • >