Supply (DP and DMP) - compact

DP-012-25

Order number: A06096

visual fault singalling

  • surge protection for all types of ELV electric and electronic equipments against surge voltage
  • installation to LV installations, close to protected equipment
  • for protection of the equipments against impact of induced overvoltages during a lightning strike or switching overvoltages

Technical parameters

Parameter name Parameter value
Type of SPD T3
Location of SPD ST 2
Mounting DIN rail 35 mm
Nominal voltage Un 12 V AC
Maximum operating voltage Uc 20.00 V AC
Maximum operating voltage Uc 20.00 V DC
Nominal load current IL 25.000 A
Maximum overcurrent protection 25 A gL/gG or C 25 A
C2 nominal discharge current (8/20 µs) per core In 2.00 kA
Test voltage L+ - L- 4.0 kV
Test voltage L+(L-)-PE 4.0 kV
voltage protection level L+ - L- 0.18 kV
voltage protection level L+(L-)-PE 0.55 kV
C2 voltage protection level mode core-PE at In Up 550 V
C2 voltage protection level mode core-core at In Up 180 V
Response time L+ - L- 25 ns
Response time L+(L-)-PE 100 ns
Connection (input - output) terminals-terminals
Cross-section of connected conductors solid (max) 6.00 mm2
Cross-section of connected conductors stranded (max) 6.00 mm2
Fault indication red indicator
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 80 °C
Humidity 5 - 95 %
According to standard EN 61643-11:2012, IEC 61643-11:2011
ETIM Class EC000942
Customs tariff number 85363030
EAN 8595090560968

Files for download

  • Product dimensions

  • Basic circuit diagram