Supply (DP and DMP) - with signalling line
DMP-012-V/1-JFR1
Order number: A05802pluggable module, coupling impedance (R – resistance) in part of data, line separated from protective earth via GDT
- surge protection of 3-core line comprehend signal transmission and supply
- installation close to protected equipment
- for protection of interfaces of I&C, electronic security and fire detection systems, etc., mainly for measuring circuits and sensors where signal and supply are transmited in one cable, against surge voltage
- single common wire for power supply and signal transmission
Technical parameters
| Parameter name | Parameter value | |
|---|---|---|
| Cross-section of connected conductors solid (min) | 0.14 mm2 | |
| Cross-section of connected conductors solid (max) | 4.00 mm2 | |
| Cross-section of connected conductors stranded (min) | 0.14 mm2 | |
| Cross-section of connected conductors stranded (max) | 2.50 mm2 | |
| Fault indication | red indicator | |
| Degree of protection | IP 20 | |
| Range of ambient temperatures (min/max) | -40 / 70 °C | |
| Humidity | 5 - 95 % | |
| According to standard | EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 | |
| ETIM Class | EC001473 | |
| Plug module | DMP-012-V/1-J-0 | |
| Nominal voltage | Un | 12 V AC |
| Maximum operating voltage | Uc | 11.00 V AC |
| Maximum operating voltage | Uc | 16.00 V DC |
| Nominal load current | IL | 16.000 A |
| Maximum overcurrent protection | 16 A gL/gG nebo B 16 A | |
| C2 nominal discharge current (8/20 µs) core-core | In | 2.00 kA |
| Test voltage L+(L-)-PE | 4.0 kV | |
| Test voltage M-PE | 4.0 kV | |
| voltage protection level L+(L-)-PE | 0.75 kV | |
| voltage protection level M-PE | 0.75 kV | |
| C2 voltage protection level mode M-PE at In | 750.00 V | |
| C2 voltage protection level mode core-PE at In | Up | 750 V |
| Response time L+(L-)-PE | 100 ns | |
| Response time M-PE | 100 ns | |
| Nominal voltage | Un | 12 V DC |
| Maximum operating voltage | Uc | 11.00 V AC |
| Maximum operating voltage | Uc | 16.00 V DC |
| Nominal load current | IL | 1.000 A |
| Treshold frequency core-core | 2.00 MHz | |
| Serial resistance per core | R | 0.80 Ω |
| C2 nominal discharge current (8/20 µs) GND-PE | 10.00 kA | |
| C2 nominal discharge current (8/20 µs) core-PE | In | 10.00 kA |
| C2 nominal discharge current (8/20 µs) per core | In | 10.00 kA |
| C3 nominal discharge current (10/1000 µs) GND-PE | 10.00 A | |
| C3 nominal discharge current (10/1000 µs) core-PE | 10.00 A | |
| C3 voltage protection level mode GND-PE at 1 kV/µs | 550.00 V | |
| C3 voltage protection level mode core-GND at 1 kV/µs | 22.00 V | |
| Response time core-GND | 1 ns | |
| Response time core-PE | ta | 1 ns |
| Response time GND-PE | 100 ns | |
| Customs tariff number | 85363010 | |
| EAN | 8595090558026 |