DMP-012-V/1-FR1

DMP-012-V/1-FR1

Describe first line
pluggable module, coupling impedance (R – resistance) in part of data, line separated from protective earth via GDT
Product description
  • combination of two-stage surge protection of 2-core signalling line in data part and surge protection for ELV in supply part
  • installation close to protected equipment
  • for protection of interfaces of I&C, electronic security and fire detection systems, etc., mainly for measuring circuits and sensors where signal and supply are transmited in one cable, against surge voltage
Ordering number
A05798
Dimension drawing
Basic circuit diagram

Technical specifications

Type of SPD
Cross-section of connected conductors solid (min)
0,14
mm2
Cross-section of connected conductors solid (max)
4,00
mm2
Cross-section of connected conductors stranded (min)
0,14
mm2
Cross-section of connected conductors stranded (max)
2,50
mm2
Fault indication
red indicator
Degree of protection
IP 20
Range of ambient temperatures - min
-40
°C
Range of ambient temperatures - max
70
°C
According to standard
EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
Plug module
DMP-012-V/1-0
ETIM Class
EC001473
Customs tariff number
85363010
EAN
8595090557982

Line part

Connection (input - output)
terminals-terminals
Location of SPD
ST 2+3
Nominal voltage
Un
12
V DC
Maximum operating voltage
Uc
11,00
V AC
Maximum operating voltage
Uc
16,00
V DC
Nominal load current
IL
1,000
A
C2 nominal discharge current (8/20 µs) per core
In
10,00
kA
C2 nominal discharge current (8/20 µs) GND-PE
10,00
kA
C2 total discharge current (8/20 µs) cores-PE
ITotal
20,00
kA
C3 nominal discharge current (10/1000 µs) core-core
In
10
A
C3 nominal discharge current (10/1000 µs) GND-PE
10,00
A
C3 nominal discharge current (10/1000 µs) core-PE
10,00
A
C3 voltage protection level mode core-core at 1 kV/µs
Up
22
V
C3 voltage protection level mode GND-PE at 1 kV/µs
550,00
V
C3 voltage protection level mode core-GND at 1 kV/µs
22,00
V
Response time core-core
ta
1
ns
Response time GND-PE
100
ns
Response time core-GND
1
ns
Serial resistance per core
R
0,80
Ω
Treshold frequency core-core
f
2,00
MHz

Power part

Nominal voltage
Un
12
V AC
Maximum operating voltage
Uc
11,00
V AC
Maximum operating voltage
Uc
16,00
V DC
Nominal load current
IL
16,000
A
C2 nominal discharge current (8/20 µs) core-core
In
2,00
kA
C2 voltage protection level mode core-core at In
Up
180
V
C2 voltage protection level mode core-PE at In
Up
950
V
C2 voltage protection level mode M-PE at In
750,00
V
Test voltage L+ - L-
4,0
kV
Test voltage L+(L-)-PE
4,0
kV
Test voltage M-PE
4,0
kV
voltage protection level L+ - L-
0,18
kV
voltage protection level L+(L-)-PE
0,95
kV
voltage protection level M-PE
0,75
kV
Maximum overcurrent protection
16 A gL/gG nebo B 16 A
Response time L+ - L-
25
ns
Response time L+(L-)-PE
100
ns
Response time M-PE
100
ns

Other products in this category

Ordering number:
A05802
  • surge protection for 3-core line (combination of signal and supply lines), instalation close to protected equipment, signal ground separated from protective earth
  • 12 V DC, pluggable module, floating
Ordering number:
A05799
  • combination of surge protections for signal and supply lines, instalation close to protected equipment, signal ground separated from protective earth
  • 24 V DC, pluggable module, floating
Ordering number:
A05803
  • surge protection for 3-core line (combination of signal and supply lines), instalation close to protected equipment, signal ground separated from protective earth
  • 24 V DC, pluggable module, floating