SP-T2+T3-320/Y-CLT-LED

SP-T2+T3-320/Y-CLT-LED

Describe first line
fault signalling by supply interruption
Product description
  • surge arrester especially for LED lights
  • installation close to protected equipme in LV power circuits
  • also for equipment in external part of building with high exposure level (according to IEEE C62.41.2)
Ordering number
A06044
Dimension drawing
Basic circuit diagram
Technical specifications
Type of SPD
T2,T3
Nominal voltage
Un
230
V AC
Maximum operating voltage
Uc
320,00
V AC
Nominal load current
IL
10,000
A
Nominal discharge current (8/20 µs) L-N
In
5,00
kA
Nominal discharge current (8/20 µs) N-PE
In
5,00
kA
Maximum discharge current (8/20 µs) L-N
Imax
10,00
kA
Maximum discharge current (8/20 µs) N-PE
Imax
10,00
kA
Test voltage L-N
Uoc
10,0
kV
Test voltage N-PE
Uoc
10,0
kV
Test voltage L-PE
Uoc
10,0
kV
Voltage protection level mode L-N
Up
1,30
kV
Voltage protection level mode N-PE
Up
1,50
kV
Voltage protection level mode L-PE
Up
1,50
kV
Short-circuit current rating
ISCCR
3,0
kA
Maximum overcurrent protection
32 A gL/gG or C 32 A
Response time L-N
ta
25
ns
Response time N-PE
ta
100
ns
TOV 5 s L-N
335
V
TOV 5 s L-PE
440
V
TOV characteristic (TOV 5 s)
withstand
TOV 120 min L-N
440
V
TOV characteristic (120 min)
withstand
TOV 200 ms L-PE
1 455
V
TOV 200 ms N-PE
1 200
V
TOV characteristic (TOV 200 ms)
safe failure
Cross-section of connected conductors solid (max)
2,50
mm2
Cross-section of connected conductors stranded (max)
1,50
mm2
Fault indication
loss of voltage, dark grey indication field
Degree of protection
IP 20
Range of ambient temperatures - min
-40
°C
Range of ambient temperatures - max
80
°C
According to standard
EN 61643-11:2012, IEC 61643-11:2011
ETIM Class
EC000942
Customs tariff number
85363030
EAN
8595090560449