MOV

SLP-PV700 V/Y S

Order number: A03669

pluggable module, visual fault signalling, module locking, remote fault signalling

  • varistor surge arrester in 'Y' connection
  • for protection of PV systems where the separating spark-over distance is kept or without LPS
  • maximum continuous operating voltage for PV application: UCPV ≥ 1.2x UOC STC

Technical parameters

Parameter name Parameter value
Type of SPD PV T2
Mounting DIN rail 35 mm
Maximum operating voltage mode 1/3, 2/3 UCPV 750.00 V DC
Short-circuit current rating ISCPV 1 000 A DC
Nominal discharge current (8/20 µs) In 20.00 kA
Maximum discharge current (8/20 µs) Imax 40.00 kA
Voltage protection level mode 1/2 Up 3.60 kV
Voltage protection level mode 1/3, 2/3 Up 3.60 kV
Response time ta 25 ns
Cross-section of connected conductors solid (min) 1.00 mm2
Cross-section of connected conductors solid (max) 35.00 mm2
Cross-section of connected conductors stranded (min) 1.00 mm2
Cross-section of connected conductors stranded (max) 25.00 mm2
Cross-section of remote indication conductors solid (max) 1.5 mm2
Cross-section of remote indication conductors stranded (max) 1.5 mm2
Fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250V/0,5A AC,250V/0,1A DC
Degree of protection IP 20
Range of ambient temperatures (min/max) -40 / 80 °C
According to standard EN 50539-11:2013
ETIM Class EC000941
Plug module SLP-PV350Y V/0
Customs tariff number 85363030
EAN 8595090536697

Files for download

  • Product dimensions

  • Basic circuit diagram

Replacement module