FX-090 F75 T F/F

FX-090 F75 T F/F

Describe first line
F connectors, 75 ohm
Product description
  • lightning current arrested with floating shielding (separated with GDT)
  • installation at the boundary of LPZ 0 and LPZ 1 zones at the line entry into building
  • for protection of coaxial lines of TV and CCTV systems, suitable as the 1st level of surge for protection in coordination with the SX type
  • in the scope of delivery: universal plastic adapter for mounting on DIN rail and GND 2 holder
Ordering number
A03387
Dimension drawing
Basic circuit diagram
Technical specifications
Type of SPD
D1,C2
Location of SPD
ST 1
Maximum operating voltage
Uc
70,00
V DC
Nominal load current
IL
4,000
A
C2 nominal discharge current (8/20 µs) core-SH
In
10,00
kA
C2 nominal discharge current (8/20 µs) SH-PE
In
10,00
kA
D1 impulse discharge current (10/350 µs) core-SH
Iimp
2,50
kA
D1 impulse discharge current (10/350 µs) SH-PE
Iimp
2,50
kA
C3 voltage protection level mode core-SH at 1 kV/µs
Up
600
V
C3 voltage protection level mode SH-PE at 1 kV/µs
Up
600
V
Impedance
Z
75
Ω
Insertion loss
0,20
dB
VSWR typ. (max.)
1,3
Frequency range - min
f
0,00
MHz
Frequency range - max
f
2 150,00
MHz
Response time core-SH
ta
100
ns
Response time SH-PE
ta
100
ns
Connection (input - output)
F 75
Degree of protection
IP 20
Range of ambient temperatures - min
-40
°C
Range of ambient temperatures - max
80
°C
Mounting
DIN rail 35 mm
According to standard
EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
ETIM Class
EC001466
Customs tariff number
85363010
EAN
8595090533870

Other products in this category

Ordering number:
A03385
  • lightning current arrester for coaxial lines (aerial antenna), installation at the entry into building
  • up to 70 V, connectors BNC 75 ohm
Ordering number:
A03390
  • lightning current arrester for coaxial lines (aerial antenna), installation at the entry into building
  • up to 180 V, connectors BNC 75 ohm
Ordering number:
A03392
  • lightning current arrester for coaxial lines (aerial antenna), installation at the entry into building
  • up to 180 V, connectors F 75 ohm