pluggable module, coupling impedance (R – resistance)
Product description
  • coarse and fine surge protection of 2-core telecommunication, data and other lines
  • installation at the boundary of LPZ 0 and LPZ 1 zones at the line entry into building
  • for protection of communication interfaces of I&C, electronic security and fire detection systems, etc. (mainly the measuring circuits) against impact of surge voltage
  • coarse and fine surge protection in differential mode (core – core) and coarse protection in common mode (core – PE)
Ordering number
A05419
Dimension drawing
Basic circuit diagram
Technical specifications
Type of SPD
D1,C2
Location of SPD
ST 1+2+3
Mounting
DIN rail 35 mm
Nominal voltage
Un
6
V DC
Maximum operating voltage
Uc
6,00
V AC
Maximum operating voltage
Uc
8,50
V DC
Nominal load current
IL
1,000
A
Treshold frequency core-core
f
1,20
MHz
Serial resistance per core
R
0,80
Ω
D1 impulse discharge current (10/350 µs) per core
Iimp
2,50
kA
D1 total discharge current (10/350 µs) cores-PE
ITotal
5,00
kA
C2 nominal discharge current (8/20 µs) per core
In
10,00
kA
C2 total discharge current (8/20 µs) cores-PE
ITotal
20,00
kA
C3 nominal discharge current (10/1000 µs) core-PE
ISM
10
A
C3 nominal discharge current (10/1000 µs) core-core
ISM
10
A
C3 voltage protection level mode core-PE at 1 kV/µs
Up
550
V
C3 voltage protection level mode core-core at 1 kV/µs
Up
12
V
Response time core-core
ta
1
ns
Response time core-PE
ta
100
ns
Connection (input - output)
terminals-terminals
Cross-section of connected conductors solid (min)
0,14
mm2
Cross-section of connected conductors solid (max)
4,00
mm2
Cross-section of connected conductors stranded (min)
0,14
mm2
Cross-section of connected conductors stranded (max)
2,50
mm2
Degree of protection
IP 20
Range of ambient temperatures (min/max)
-40 / 70 °C
According to standard
EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012
ETIM Class
EC001466
Plug module
BDG-006-V/1-0
Customs tariff number
85363010
EAN
8595090554196

Other products in this category

Ordering number:
A06467
lightning current arrester with coarse and fine surge protection for up to 4-core shielding floating signalling lines, installation at the line entry into building and also installation close to protected device, 6 V DC, max. 1 A, replacement module, line separated from protective earth via GDT
Ordering number:
A05704
lightning current arrester combined with fine surge protection for shielded 2-core signalling lines, signal ground separated from protective earth, installation at the entry into building close to the protected equipment, 6 V DC, max. 1 A, pluggable module, floating
Ordering number:
A06469
lightning current arrester with coarse and fine surge protection for 2-core shielding floating signalling lines, installation at the line entry into building and also installation close to protected device, 6 V DC, max. 2 A, replacement module, line separated from protective earth via GDT
Ordering number:
A06472
lightning current arrester with coarse and fine surge protection for two 2-core shielding floating signalling lines, installation at the line entry into building and also installation close to protected device, 6 V DC, max. 1 A, replacement module, line separated from protective earth via GDT
  •  
  • 1 of 14
  • >